Experience reliable circuit disconnection with the IMO DC Isolator 16A 800VDC - 4 Pole. This robust isolator is perfect for high-voltage applications, ensuring safety during maintenance. Its easy installation and durable design make it an essential component for solar power systems and battery storage units. Enhance your installations today.
You need to log in to access the data sheet, user manual, and warranty info.
The IMO SI16-PEL64R-4 is a four-pole TRUE DC solar isolator for PV-array DC disconnection. It combines an enclosed PEL64R body, lockable rotary handle and operator-independent switching mechanism for DC switch-disconnector duties.
Suffix 4 identifies the standard four-pole arrangement shown for two PV strings. It is distinct from suffix 4S, which is the four-poles-in-series configuration.
The PEL64R SI16 2/4-pole derating graph supports 16A at 800VDC in DC21B/DC-PV1 duty with 2.5mm² conductors up to approximately 35°C ambient; derating applies above this temperature.
PEL64R is the enclosed version with a lockable rotary handle and IP67 / NEMA 4X protection.
The operator-independent mechanism uses knife-edge contacts and arc-suppression chambers; the catalogue states 3ms typical and 5ms maximum arc-suppression time. The SI range is polarity independent.
For enclosed products, the main plastic enclosure is rated UL 94 V-0 and the handle UL 94 V-2.
Model SI16-PEL64R-4. Rated thermal current 16A; 16A at 800VDC in DC21B/DC-PV1 duty subject to the stated PEL64R temperature/conductor derating. Rated insulation voltage Ui is 1500V for minimum-IP55 installation, impulse withstand voltage Uimp 8kV and contact distance 8mm per pole. Rated conditional short-circuit current is 5kA with a 40A maximum gL/gG fuse. One-second withstand current and short-circuit making capacity are each 800A for the standard four-pole configuration. Mechanical life is 10 × 10³ operations. Maximum conductor sizes are 4–16mm² solid/stranded and 4–10mm² flexible; terminal screw M4 Pz2; tightening torque 1.7–1.8Nm. Contact resistance is 1.75mΩ per pole and power loss for four poles at 16A is 2W. PEL64R operating temperature is −40°C to +45°C and storage temperature −50°C to +90°C. Dimensions are 180 × 98 × 107mm. The SI16 approvals table marks RoHS, UL508i, UL508, CE, CCC and IEC CB Europe; technical data is stated to IEC 60947-3, VDE 0660 and GB14048.3.
Use as a DC-side PV switch-disconnector in the four-pole configuration shown by IMO. For the 16A at 800VDC rating, use 2.5mm² conductors and observe the PEL64R derating curve above approximately 35°C; the enclosed-unit ambient limit is +45°C. Tighten the M4 Pz2 terminals to 1.7–1.8Nm and select conductor size within the stated limits.
Weight (kg)
0.42
Manufacturer
IMO Precision Controls
Commodity Code
8536508090
Dimensions (mm) (H x W x D)
180 x 98 x 107
Get a Quote for
Are you sure you would like to remove this item from the shopping cart?