Mersen MB000 125A 3P Bottom/Panel Mount Fuse Switch Disconnector

Mersen SKU: D1070423

More Details
The Mersen MB000 125A 3P Panel is a compact and reliable NH fuse switch disconnector designed for bottom fitting panel installations. With a 125A rating, IP30 protection, and triple-pole switchability, it ensures secure and efficient electrical distribution in various applications.
Documents

Mersen MB000 125A 3P Bottom/Panel Mount Fuse Switch Disconnector

The Mersen MULTIBLOC 000.ST9 is a size 000, triple-pole NH fuse switch disconnector for bottom fitting or panel installation. Item D1070423 has a 125A conventional free-air thermal current with NH fuse-links and a rated operational voltage of 690VAC; at 690VAC its documented AC21B operational current is 80A.

Key Features
Triple-pole size 000 switching

Three-pole unit for coordinated switching of NH size 000 fuse-links to IEC/EN 60269-2 and VDE 0636-2.

AC and DC utilisation ratings

AC ratings include AC23B at 400V/100A, AC22B at 400V/125A and 500V/100A, AC21B at 500V/125A and 690V/80A. DC ratings are 250V/125A DC22B with all poles in series and 250V/80A DC21B with L1/L3 in series.

IP30 touch protection

IP30 protection, large inspection windows with test holes, and integrated padlocking and sealing facilities.

2.5–50mm² frame clamps

Six frame clamps provide cable termination for conductors from 2.5 to 50mm².

Safe on-load operation

Connection and disconnection on load are supported in accordance with IEC/EN 60947-3 and the stated utilisation categories.

Benefits
  • Bottom-fitting design supports compact panel and distribution-board installation.
  • Triple-pole operation switches all three phases together.
  • Integrated padlocking and sealing support controlled isolation.
  • Large windows and test holes assist inspection and electrical testing.
Technical Summary

Mersen MULTIBLOC 000.ST9, catalog 1.005.070, item D1070423. Three poles, size 000, 125A conventional free-air thermal current with NH fuse-links, 160A with solid links, 690VAC rated operational voltage and 250VDC rating. At 690VAC the AC21B operational current is 80A. Rated insulation voltage Ui is 1000V, impulse withstand voltage Uimp 6kV, frequency 50–60Hz, protection IP30, pollution degree 3 and rated duty uninterrupted. Short-circuit making capacity with solid links is 5.1kA peak; short-time withstand current is 3.5kA for 1 second. Conditional short-circuit current with fuse-links is 80kA at 500VAC/125A, 80kA at 690VAC/80A and 25kA at 250VDC/125A. Frame-clamp capacity is 2.5–50mm². Closed dimensions are 216 × 53 × 79.5mm; the open-door envelope is 227mm. Product weight is 0.43kg. Standard IEC/EN 60947-3; compatible NH fuse-links to IEC/EN 60269-2 and VDE 0636-2.

Installation Notes

Install by bottom fitting or panel mounting. The closed body is 216mm high, 53mm wide and 79.5mm deep; allow up to 227mm depth for the open switch door. A DIN-rail adapter is available separately for 35 × 7.5mm and 35 × 15mm rails to DIN EN 60715. Use compatible size 000 NH fuse-links and 2.5–50mm² conductors in the six supplied frame clamps.

Efficiency

Maximum permitted fuse-link power dissipation is 9W. Device power dissipation without NH fuse-links is 8W at 100A load and 13W at 125A load; maximum solid-link power dissipation is 1.2W.

Manufacturer

Mersen

Commodity Code

8541900000

Dimensions (mm) (H x W x D)

216 x 53 x 79.5

Weight (kg)

0.43