Emlite 1 Phase Meter 100A (Pulsed) with Extended Cover

Emlite SKU: ECA.2 c/w
More Details

The Emlite 1 Phase Meter 100A Pulsed with Extended Cover offers precise energy monitoring for both residential and commercial use. With a maximum current rating of 100A and a pulsed output for easy integration, this compact meter ensures effective energy management while providing added protection against environmental factors.

Documents

Emlite ECA2.V 100A single-phase pulsed electricity meter

The Emlite ECA2.V is the four-terminal ECA2 variant with an electronic pulsed output and no Net Register. It is a compact wall-mounted meter for single-phase billing, consumption monitoring or micro-generation metering, supplied with the extended terminal cover.

Technical specification

  • Supply: single phase, 1 phase 2 wire (1p2w), direct connected
  • Nominal voltage: 220–240VAC; maximum stated by the Emlite technical sheet: 276V
  • Voltage withstand: 415V for a maximum of 6 hours
  • Nominal frequency: 50Hz with ±5% variation
  • Maximum current (Imax): 100A
  • Approved Imin–Iref(Imax) configurations: 0.25–5(100)A, 0.5–10(100)A, 0.75–15(100)A or 1–20(100)A
  • Active-energy accuracy: Class B (1%) to EN 50470-1 and EN 50470-3
  • LED metrology pulse constant: 1000 imp/kWh
  • LCD energy register; optical port for configuration or electronic meter reading
  • Ingress protection: IP52; insulation protective class: Class II
  • Impulse-voltage rating: 6kV; AC voltage rating: 4kV
  • Operating temperature range: −40°C to +70°C; intended location: indoor
  • Main terminals: solid brass, 8.2mm diameter; terminal arrangement: BS 7856 / BS
  • Wall-mounted extended-cover dimensions (H × W × D): 129 × 125 × 39.9mm
  • UKCA type-examination certificate 0120/SGS0103/UK, Issue 4, valid until 22 March 2030
  • Exact variant function: electronic pulsed output; no Net Register
  • Electrical pulsed-output connections: auxiliary terminal 5 (+) and terminal 6 (−)
  • Typical generation-meter configuration: one total-generation register, normally the IMP register

Metering and installation

The ECA2.V measures active energy and can be configured for the required import/export register presentation, but it does not calculate a NET energy value. For normal solar-generation use, follow the ECA2.z/.v wiring arrangement in the manufacturer guide and do not use the ECA2.nz/.nv NET-meter connection diagram.

Manufacturer

Emlite

Commodity Code

9028301100

Dimensions (mm) (H x W x D)

125 x 125 x 40

Weight (kg)

0.31

PDF Icon

User Guide Emlite ECA2 Solar PV And Battery Storage

PDF Icon

Datasheet Emlite 1 Phase

PDF Icon

6655

Write Your Own Review
You're reviewing: Emlite 1 Phase Meter 100A (Pulsed) with Extended Cover
loader
Loading...

check-circle You submitted your review for moderation.